What Custom Poller values for APC UPS UpsAdvinputLineVoltage alert using 'Gauge' values to show Voltage

1.) Set up custom pollers for monitoring APC UPS devices, which work fine.

2.) Building 'Custom Node Poller' (See attached), to trigger alerts based on specific 'status' or 'numeric status' based on values.

3.) Last poller alert shown with red circle is for upsAdvInputLineVoltage, which I want to trigger when line voltage drops below, say 119v. However, not sure if a.) this is the best poller to use for this, and b.) if I can simply use a 'raw' value example like 118 for voltage and expect it to work properly.  The OID shows this is a 'Gauge' value with a range from 0 to 4294967295. (For reference, this was the same value range shown for 'TimeTicks' under poller preceeding it for upsAdvBatteryRunTimeRemaining. The solution there, was conversion of the timeticks (1/100th second), to a roughly 5 minute value which is 30000 (shown is 30060).

 

Suggestions or recommendations appreciated.